Online double conversion UPS
Power rang :(1-10kVA) pf:0,9
HF online UPS Single phase for Centralized server center, mainframe, network control center, computing center
| MODEL | |
| Phase | Single phase with ground |
| Capacity | 1000 VA – 10000 VA |
| INPUT | |
| Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
| Input voltage range | 60-150VAC or 120-300VAC (Based on load at 50%) 90-140VAC or 180-280VAC (Based on load at 100%) |
| Frequency range | 40Hz ~ 70 Hz |
| Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
| OUTPUT | |
| Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
| Voltage tolerance | ± %1 |
| Frequency range | 47~ 53 Hz or 57 ~ 63 Hz |
| Frequency range (batt. mode) | 50 Hz or 60Hz ± %0.5 |
| Output current crest factor | 3:1 |
| THD | ≤ %3 THD (linear load) ≤ %6 THD (non-linear load) |
| Transfer time | AC Mode -> Battery Mode | Zero |
| Transfer time | Inverter -> bypass | 4 ms |
| Waveform (batt. mode) | Pure sinewave |
| EFFICIENCY | |
| AC Mode | %94 |
| Battery Mode | %91 |
| BATTERY | |
| Standard model | Battery type | 12V / 9AH |
| Sta2ndard model | Numbers | 2 – 20 PCS |
| Standard model | Typical recharge time | 4 hours recover to 90% capacity |
| Standard model | Charging current (max.) | 1.0 A |
| Standard model | Float charging voltage | 27.4VDC – 270 VDC ± %1 |
| INDICATORS | |
| LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
| ALARM | |
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| ENVIRONMENT | |
| Relative humidity | 20%-90 RH @ 0- 40°C (noncondensing) |
| Noise level | < 50dBA @ 1 meter |
| Managament | |
| Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
| Optional SNMP | Power management from SNMP manager and web browser |