3 phase input / 1 phase output :
| TECHNICIAL SPECIFICATIONS | |
| Phase | 3 phase in / 1 phase out |
| Capacity | 10000 VA -20000VA |
| INPUT | |
| Nominal Voltage | 3x400VAC (3F+N) |
| Input voltage range | 190-520VAC (3-Phase) @ %50 Load 305-520VAC (3-Phase) @ %100 Load |
| Frequency range | 46Hz ~ 54 Hz |
| OUTPUT | |
| Voltage | 208/220/230/240VAC |
| AC Voltage regulation | ± %1 |
| Frequency range | 46 ~ 54Hz |
| Frequency range (batt. mode) | 50Hz ± 0.1Hz |
| Output current crest factor | 3:1 |
| THD | ≤ %3 THD (Linear Load) ≤ %5 THD (Non-linear Load) |
| Transfer time | AC Mode -> Battery Mode | Zero |
| Transfer time | Inverter -> bypass | Zero |
| Waveform (batt. mode) | Pure Sinewave |
| EFFICIENCY | |
| AC Mode | %91 |
| Battery Mode | %91 |
| BATTERY | |
| Standard model | Battery type | 12V / 9AH |
| Standard model | Numbers | 16 pcs – 20 pcs |
| Standard model | Typical recharge time | 9 hours recover to 90% capacity |
| Standard model | Charging current (max.) | 1A ± %10 |
| Standard model | Float charging voltage | 218.4 VDC ± %1 – 273 VDC ± %1 |
| INDICATORS | |
| LCD panel | UPS status, Load level, Input/Output voltage, Discharge timer, and Fault conditions |
| ALARM | |
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| ENVIRONMENT | |
| Relative humidity | %0-95 RH @ 0-50°C (non-condensing) |
| Noise level | < 60dBA @ 1 meter |
| Management | |
| Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, 7/8, Linux and MAC |
| Optional SNMP | Power management from snmp manager and web browser |